ControlPlus

Total solution providers for natural gas systems…


EXPERIENCE
INDUSTRIAL SKIDS, FILTERS
DRS
(District Regulating Skids)
CGS
(City Gate Stations)
ODORIZERS
REFURBISHMENT, etc.
 
Gas Conditioning & Regulating Skid
Client : ADANI ENERGY LTD.
Process Condition :
Flow : 150 SCMH
Filtration Efficiency : 100% for solid & droplet removal 5 micron
Temperature : 0 to 50°c
Inlet Pressure : 19 to 26 Barg
Controlled Pressure : 1.5 Barg
Line Size : Inlet : 1.5" X 300#
Outlet : 2" X 150#
Station Design as per IGE-TD-13
Piping Design as per ASME code B 31.8 for Gas Transmission and Distribution Piping System
Major Equipments :
a) Vertical Dry Gas Filter Designed as per Section VIII, Div.1.
b) Slam Shut Valves Tartarini – BM5 Series
c) Regulators –Fisher Make – EZR Series
d) Safety Valves – Sebim Valves
e) Gauges – Pressure and Differential Pressure Gauges
Design Description :
Single stream, Wide-open Monitor configuration, Creep relief in the downstream, Enclosed in a thick lockable cabinet with glass windows for easy visibility of the meter, supported on approx. 0.5 mtr. Leg supports for easy installation and access for maintenance.
Back   Next