Gas Conditioning & Regulating Skid
Client : GUJARAT GAS COMPANY LTD.
Process Condition :
Flow : 3200 ~ 60,000 SCMD.
Filtration Efficiency : 100% for solid & droplet removal 5 micron
Temperature : 0 to 50°c
Inlet Pressure : 10 to 85 Barg.
Controlled Pressure : 7 - 10 Barg.
Line Size : Inlet : 4" X 600#
Outlet : 4" X 150#
Station Design as per IGE-TD-13
Piping Design as per ASME code B 31.8 for Gas Transmission and Distribution Piping System
Major Equipments :
a) Vertical Dry Gas Filter Separator Designed as per Section VIII, Div.1.
b) Slam Shut Valves - Tartarini, Emerson Make
c) Regulators – Tartarini – FL Series
d) Ultrasonic Meter – Emerson Make
e) Gauges, Transmitters – Wika and Emerson Make
Design Description :
Twin stream, Working Monitor configuration, Working-standby stream system, Creep relief in the downstream, Ultrasonic Flow Metering and Flow Control were an integral part of the skid. The instruments on the skid were connected to a Flow Computer and RTU configurable to SCADA network of client.